PLC

1746-OV16 AB

1746-OV16

Description: Allen Bradley 1746-OV16 is an SLC 500 discrete current output module. This module has sixteen (16) channels and can provide a nominal output voltage of 24VDC and an output voltage range of 10-50VDC. It has one (1) set of 16 channels and a backplane current consumption of 0.270 A. Its continuous output current at each point is 0.50 A at 30 ° C (86 ° F) and 0.25 A at 60 ° C (140 ° F)

 

Get A Quote
Contact Us

1746-OV16 AB

About 1746-OV16

1746-OV16 is a discrete output module manufactured by Allen Bradley. This module provides sixteen (16) output channels in one (1) channel group. It is a current injection output module that provides a range of 10-50VDC output voltage, with a minimum output of 24VDC. This module is very suitable for supplying power to DC loads, such as relay coils, indicating and sounding devices.

The backplane current consumption of 1746-OV16 at 5VDC is 0.270 amperes, the off state leakage current is 1 mA, and the minimum load current is also 1 mA. Each channel of this output module has a signal delay of 0.1 ms for ON to OFF conversion and 1.0 ms for OFF to ON conversion. The continuous output current of this module at each point is 0.50 A at 30 ° C (86 ° F) and 0.25 A at 60 ° C (140 ° F), while the continuous output current of each module is 8.0 A at 30 ° C (86 ° F) and 4.0 A at 60 ° C (140 ° F). The maximum on state voltage drop of this module at 0.5 A is 1.2V. one thousand seven hundred and forty-six

-The surge current at each point of OV16 is 3.0 A, lasting for 10 ms. The repeatability at 60 ° C (140 ° F) can be repeated every 1 second at 30 ° C (86 ° F) and 2 seconds.

1746-OV16 is installed on the SLC 500 chassis. It is a single slot width module that is directly connected to modular style SLC 500 hardware. It comes with a detachable wiring terminal pre installed on the module. This junction box can be removed from the module for easier and faster wiring activities.

It is a 16 channel output module compatible with the SLC 500 system. 0.388W heat dissipation per point, with a total heat dissipation of 7.6W. 1746-OV16 has a detachable junction box that allows you to easily connect or modify wiring on the module. Its working voltage range is 10-50V DC. Its backplane current consumption (0.27 A) is higher than that of the 1746-OV8 and 1746-OVP16 modules. The maximum signal delay of 1746-OV16 is 0.1 milliseconds in the on state and 1 millisecond in the off state. Its continuous current for each output and module is 0.5A and 8A at 30 ° C, and 0.25A and 4A at 60 ° C. The maximum off state leakage current of 1746-OV16 is 1 mA, and the maximum on state voltage drop is 1.2V (0.5A and 3A, with a maximum surge current of 10ms per point).