350015-05-05-CN BENTLY
3500/15-05-05-CN Program Requirements for Verifying Channel Values and Angular Frequencies
You use the following formula to calculate the verification frequency:
Find the center of the bandpass frequency range. Input configured high
Enter through filter corner frequency and low-pass filter corner frequency
The formula is as follows:
3500/15-05-05-CN Vibration Frequency=(0.89 * HPF)+(01575xLPF)
HPF=High pass filter corner frequency
LPF=Low pass filter corner frequency
If filtering is not configured, set the frequency of the function generator to 100
Hertz.
If a low-pass filter is configured but not a high-pass filter, use the
The following determines the HPF to use in the formula:
-If the unit is RMS, a 10 Hz HPF is used. For any other configuration, use the
3 Hz high pass filter.
If a high pass filter is configured without a low pass filter, use the
5500 Hz low-pass filter.
The general method for testing OK limits for the 3500/15-05-05-CN is to disconnect the input. at present
Causes an abnormal condition and the OK relay to change state (power down).
According to Section 5.1.7.1 (Testing
Device and Software Settings – Speed).
Disconnect the SIG/A field wiring from the channel terminal
Proximitor/Seismic Monitor 1/0 Module.
3. Confirm that the OK relay changes state (power off).
4. Confirm that the channel normal status line on the 3500/15-05-05-CN verification screen displays No
5. Okay.
Reconnect the SIG/A field wiring to the channel terminals on the monitor
Input/output module. Press the RESET switch on the Rack Interface Module (RIM)
Verify that the OK LED is lit and that the OK relay is energized.
6. Confirm that the Channel OK Status line on the verification screen displays OK.
“If you are unable to verify any configured OK limits, go to section 5110 (if”
Channel failed validation test).
8.3500/15-05-05-CN Repeat steps 1 through 7 for all configured channels
Manufacturer: Bently Nevada Product Number: 3500/15-05-05-CN Product Type: 3500/15 Power Supply Made in the United States Can Add a Certificate of Origin (COO) Power Supply Type (Top Slot): 05=Universal AC Voltage (85 to 264 Vac rms) Power Supply Type (Bottom Slot): 05=Universal AC Voltage (85 to 264 Vac rms) CN=Country Specific Certification (The quick reference guide and on-site notification letter for CN certification options are located in the download section)
Operating temperature: – 30 ° C to+65 ° C Storage temperature: – 40 ° C to+85 ° C Humidity: 95%, Non condensing dimensions (L x W x H): 25.15 cm x 5.08 cm x 12.07 cm Shipping weight: 5 kg
YOKOGAWA VALVE FLOW COMPUTING TOTALIZER YFCT-1NN1-A1A*A
NEW THOMAS MICRON 12:1 PLANETARY GEARHEAD ATR014-012-SO
Dual Motoman Robotic System with XRC UP6 Robots
Dual Motoman System with UP 20 Robots(2004)
Dual Motoman SK6,8 Axis Robots with Camco Table
MOTOMAN UP-130 6 AXIS WELDING SPRAY ROBOTIC ROBOT ARM
Motoman Robot-Model YR-SK 120-C000
MOTOMAN UP20 ROBOT,6 AXIS,TYPE YR-UP20-A02